22 GOSSEN Mueller & Weigert
Moving-Coil Movement with Power Converter, 90˚ Scale
Narrow Bezel per DIN 43718
Front Dimensions 96 x 96 mm 144 x 144 mm
Type LM 96 LM 144
Scale Length 97 mm 150 mm
Accuracy Class 1.5 1.5
Weight (standard model), Max. 0.8 kg 1.0 kg
Consumption, Approx.
Current Path 0.2 VA 0.2 VA
Voltage Path order no.: AB1/AB2/AB12/AB5/AB15 3.0 VA 3.0 VA
AB11 3.5 VA 3.5 VA
AB4/AB14 3.4 VA 3.4 VA
AB6 3.9 VA 3.9 VA
AB16 4.3 VA 4.3 VA
Nominal Line Voltage phase-to-neutral (= operating voltage) 300 V 300 V
3-phase 3-wire systems 500 V 500 V
3-phase 4-wire systems 277/480 V 277/480 V
Test Voltage 2.2 kV 2.2 kV
Front Housing-Panel Protection IP 52 IP 52
In preparation
Type LM 96
Square Panel Meters
for Active Power or Reactive Power
Technical Data
Description
Analog panel meter with core-magnet moving-coil movement and built in power
converter for active and reactive power.
Depending upon type of system and power, the power converter consists of one,
two or three multipliers. The multipliers function in accordance with the
TDM process (time division multiplier). The output signals from the multipliers are
added and fed to the moving coil mechanism.
Reference Conditions
Notes Concerning the Determination of Measuring Ranges
The upper measuring range value should be a standard value per DIN 43701:
1 1.2 1.5 2 2.5 3 4 5 6 7.5 8
and corresponding powers of ten.
The upper measuring range value must lie within a range of 0.5 to 1.2 times apparent
power.
Apparent power S is calculated from the primary values from the current and voltage
transformers:
where U equals phase-to-phase voltage
Display
Scale Graduation Coarse-fine
Pointer Beam pointer with knife-edge
Mechanical Design
Housing Material Polycarbonate, self-extinguishing and drip-proof per UL94V-0
Mounting Fasteners Standard: S type screw clamp, except for:
Screw spindle for 144 x 144 mm panel meters
alternative:
Subklew fasteners
(except for 144 x 144 mm panel meters)
Scale Interchangeable scales
Scales may only be replaced under voltage-free conditions!
Replaceable Bezels and glass faceplates
May only be replaced under voltage-free conditions!
Terminals M4 screw terminals with self-lifting terminal clips. Screws
can be turned with cross-head or standard screw drivers.
Terminal Designation per DIN 43807
Contact Protection Hand-safe full cover included
Reference Quantities Reference Conditions
Ambient Temperature 23°C ± 2°C
Position of Use control panel vertical ±1°
Frequency 45 Hz ... 65 Hz
50 Hz ±0.1 Hz for order no.: AB11
Current Components 20 ... 120% of rated value
Voltage Components 98 ... 102% of rated value
Warm-Up Time 5 min
Other DIN EN 60051
Single-Phase AC S = U x I
Three-Phase S = 3 x U x I