Moving-Coil Movement, 90° Scale
Narrow Bezel per DIN 43718
Front Dimensions 48 x 48 mm 72 x 72 mm 96 x 96 mm 144 x 144 mm
Type DS 48 DS 72 DS 96 DS 144
Scale Length 37 mm 63 mm 97 mm 150 mm
Accuracy Class 1.5 1.5 1.5 1.5
Weight (standard model) Max. 0.12 kg 0.25 kg 0.32 kg 0.53 kg
Operating Voltage, Max. 300 V 600 V 600 V 600 V
Test Voltage 2.2 kV 3.25 kV 3.25 kV 3.25 kV
Front Housing-Panel Protection IP 52 IP 52 IP 52 IP 52
In preparation
Front in mm Nominal Dimensions Cutout Dimensions, mm Installation Depth Including Terminals (t), mm Installation Depth Including Full Cover (f), mm
a
1
x a
2
h
I
1
x I
2
≤4 A (M4) 6...25 A (M6) 40...60 A (M6) ≤4 A 6...25 A 40...60 A
48 x 48 48 x 48 5 45
+0.6
x 45
+0.6
54 72 − 62.5 75 −
72 x 72 72 x 72 5 68
+0.7
x 68
+0.7
54 67 67 62.5 70 70
96 x 96 96 x 96 5 92
+0.8
x 92
+0.8
54 67 67 62.5 70 70
144 x 144 144 x 144 8 138
+1
x 138
+1
54 67 67 62.5 70 70
Type DS 72
Square Panel Meters
for Direct Current or Direct Voltage
Technical Data
Description
Analog Panel Meter with Core-Magnet Moving-Coil Movement
and Spring-Loaded Pivot Bearings
Internal Resistance / Voltage Drop / Power Consumption
Reference Conditions
Dimensions
Display
Scale Graduation Coarse-fine
Pointer Beam pointer with knife-edge
Mechanical Design
Housing Material Polycarbonate, self-extinguishing and drip-proof per UL94V-0
or sheet metal housing for front panel dimensions of
72 x 72 mm and 96 x 96 mm as option.
Mounting Fasteners Standard: S type screw clamp, except:
Screw spindle for 144 x 144 mm panel meters
Alternatives: see next page
Scale Interchangeable scales
➲ Scales may only be replaced under voltage-free conditions!
Replaceable Bezels and glass faceplates
➲ May only be replaced under voltage-free conditions!
Terminals M4 screw terminals with self-lifting terminal clips. Screws
can be turned with cross-head or standard screw drivers,
except for:
Direct connection ammeters ≥6 A: M6 bolt terminals.
Terminal Designation “+11” and “12”, except for:
“+17” and “18” for 144 x 144 mm panel meters
Contact Protection Finger-safe full cover included
Measuring Input Ri at Zero Point Tolerance
left center
10% of
positive
upper value
1 mA 37 Ω 92 Ω 34 Ω
±10%
5 mA 2.5 Ω 18 Ω−
±10%
10 mA 18 Ω 9.5 Ω−
±10%
20 mA 3.0 Ω 1.5 Ω 2.8 Ω
±10%
4 ... 20 mA 0.7 Ω
±10%
Connection to shunt power consumption: 6 mA
±10%
lead resistance: 0.06 Ω
1 A ... 60 A voltage drop: 60 mV
±10%
≥1 V 1000 Ω /V
± 5%
Reference Quantities Reference Conditions
Ambient Temperature 23°C ± 2°C
Position of Use control panel vertical ± 1°
Other DIN EN 60051